Metric Voltage Drop Calculator

Short answer

Voltage drop is current times the resistance of the conductors carrying it. For a two-wire single-phase circuit, Vd = 2 × I × R × L; for a balanced three-phase circuit, Vd = √3 × I × R × L, where R is the conductor resistance per metre and L is the one-way length. Compare the percent drop with the limit in the Canadian Electrical Code edition your province uses.

Voltage drop
4.75 V
Percent drop
1.98 %
Voltage at load
235.2 V

Formula

Vd = k × I × (Ω/km × L ÷ 1000), k = 2 (1-phase) or √3 (3-phase)

Worked example

24 A over 30 m of conductor at 3.3 Ω/km on a 240 V single-phase circuit: R per conductor = 3.3 × 30 ÷ 1000 = 0.099 Ω, Vd = 2 × 24 × 0.099 = 4.75 V, or about 1.98 %.

Before you rely on it

  • Use the conductor resistance from the CEC tables or the manufacturer's data for the size, material and temperature you are working with. This tool does not pick a conductor size for you.
  • Percent-drop limits are set by the Canadian Electrical Code. Check the edition your province has adopted.