Red Seal Sheet Metal Worker (308A): E – Performs maintenance and repair practice questions
8 original questions on this part of the exam, each with an explanation and a reference you can check.
What this area covers (7 questions on the exam)
Performing scheduled maintenance (3) and repairing faulty systems and components (4).
Question 1 · E – Performs maintenance and repair
During scheduled maintenance of a kitchen exhaust hood system, what should be checked at the hood?
Show answer without guessing
Answer: C. Grease filters and the grease buildup in the hood and duct, cleaning as scheduled
Grease buildup in filters, the hood plenum and exhaust duct is a major fire risk. NFPA 96 sets inspection frequencies based on the type and volume of cooking, and accumulations found must be cleaned by qualified people. Refrigerant and gas work belong to other trades.
Check it: RSOS task E-18 (scheduled maintenance)
Question 2 · E – Performs maintenance and repair
A newly fabricated duct section drums loudly whenever the fan starts. What is the most likely fix?
Show answer without guessing
Answer: A. Add reinforcement such as cross-breaking, beading or stiffening angles to the panel
Drumming (oil-canning) happens when a large flat panel snaps in and out as pressure changes. Stiffening the panel with cross-breaks, beads or reinforcement angles stops it. More speed raises the pressure swing and makes drumming worse.
Check it: RSOS task E-19 (repairing faulty systems and components)
Question 3 · E – Performs maintenance and repair
A belt-driven fan has a 100 mm motor sheave and a 250 mm fan sheave. If the motor runs at 1750 r/min, what is the fan speed (ignore belt slip)?
Show answer without guessing
Answer: D. 700 r/min
Speeds are inversely proportional to sheave diameters: fan r/min = 1750 × 100 ÷ 250 = 700 r/min. A larger driven sheave slows the fan.
Check it: RSOS task E-18 (scheduled maintenance)
Question 4 · E – Performs maintenance and repair
Why are fire dampers tested periodically?
Show answer without guessing
Answer: A. To confirm they close fully and are unobstructed
Fire dampers can seize from dirt or corrosion, or be blocked by debris. Periodic inspection and drop testing at the frequency required by the fire code confirm they will close.
Check it: RSOS task E-18 (scheduled maintenance)
Question 5 · E – Performs maintenance and repair
Which is a sign that a duct system needs inspection for cleaning?
Show answer without guessing
Answer: D. Visible dust or debris at outlets and in duct
Dust discharging from outlets, debris in ducts or microbial growth indicate the need for inspection and possible cleaning to recognized industry standards.
Check it: RSOS task E-18 (scheduled maintenance)
Question 6 · E – Performs maintenance and repair
A room is getting much less air than design. Which repair check comes first?
Show answer without guessing
Answer: D. Look for closed dampers, crushed flex or leaks
Low airflow is usually caused by obstructions: closed or slipped dampers, kinked or crushed flex, disconnected duct or leaks. These are checked before any redesign.
Check it: RSOS task E-19 (repairing faulty systems and components)
Question 7 · E – Performs maintenance and repair
A downspout has come loose from the wall. What is the correct repair?
Show answer without guessing
Answer: D. Refasten it with suitable straps and anchors
Downspouts need straps fastened to the wall at intervals with anchors suited to the wall material, so wind, ice and water weight do not pull them off.
Check it: RSOS task E-19 (repairing faulty systems and components)
Question 8 · E – Performs maintenance and repair
After a renovation, a branch duct was disconnected above the ceiling. How is this best found?
Show answer without guessing
Answer: D. Trace the branch and check flows at outlets
Comparing measured outlet airflows to design and tracing the branch above the ceiling locates disconnections. Reconnecting and sealing restores airflow.
Check it: RSOS task E-19 (repairing faulty systems and components)
These are VoltExam questions written for the Red Seal Sheet Metal Worker Interprovincial Exam, not official exam questions. Take the full free practice test or read the Red Seal Sheet Metal Worker (308A) guide.
Last checked against Red Seal Program (with provincial and territorial apprenticeship authorities) on .
Practise Red Seal Sheet Metal Worker (308A) by topic
Want every Red Seal Sheet Metal Worker (308A) topic and the timed mock exams?
- ✓ 600 Red Seal Sheet Metal Worker practice questions, every answer explained and cited
- ✓ Full-length timed mock exams: 120 questions, 4 hours, scored against 70%
- ✓ Practise by topic and review every question you missed
- ✓ Every other Canadian exam on VoltExam included
From
C$8.99/month
3-day free trial · or C$44.99 once for lifetime
Try all 600 free for 3 daysFree trial for new members on the Monthly plan, then C$8.99/month until you cancel. See all plans
Official sources
- Red Seal – Sheet Metal Worker trade page ↗
- Red Seal – Sheet Metal Worker exam information (breakdown) ↗
- Red Seal – Exam Preparation Guide ↗
- Skilled Trades Ontario – Sheet Metal Worker ↗
- Skilled Trades Ontario – Sheet Metal Worker (308A) 2025 trade report ↗
Sources checked November 14, 2026. VoltExam is independent and not affiliated with Red Seal Program (with provincial and territorial apprenticeship authorities). Rules change: confirm details with the official source before your exam.