Red Seal Sheet Metal Worker (308A): E – Performs maintenance and repair practice questions

8 original questions on this part of the exam, each with an explanation and a reference you can check.

What this area covers (7 questions on the exam)

Performing scheduled maintenance (3) and repairing faulty systems and components (4).

Answered 0 / 8Score 0
  1. Question 1 · E – Performs maintenance and repair

    During scheduled maintenance of a kitchen exhaust hood system, what should be checked at the hood?

    Show answer without guessing

    Answer: C. Grease filters and the grease buildup in the hood and duct, cleaning as scheduled

    Grease buildup in filters, the hood plenum and exhaust duct is a major fire risk. NFPA 96 sets inspection frequencies based on the type and volume of cooking, and accumulations found must be cleaned by qualified people. Refrigerant and gas work belong to other trades.

    Check it: RSOS task E-18 (scheduled maintenance)

  2. Question 2 · E – Performs maintenance and repair

    A newly fabricated duct section drums loudly whenever the fan starts. What is the most likely fix?

    Show answer without guessing

    Answer: A. Add reinforcement such as cross-breaking, beading or stiffening angles to the panel

    Drumming (oil-canning) happens when a large flat panel snaps in and out as pressure changes. Stiffening the panel with cross-breaks, beads or reinforcement angles stops it. More speed raises the pressure swing and makes drumming worse.

    Check it: RSOS task E-19 (repairing faulty systems and components)

  3. Question 3 · E – Performs maintenance and repair

    A belt-driven fan has a 100 mm motor sheave and a 250 mm fan sheave. If the motor runs at 1750 r/min, what is the fan speed (ignore belt slip)?

    Show answer without guessing

    Answer: D. 700 r/min

    Speeds are inversely proportional to sheave diameters: fan r/min = 1750 × 100 ÷ 250 = 700 r/min. A larger driven sheave slows the fan.

    Check it: RSOS task E-18 (scheduled maintenance)

  4. Question 4 · E – Performs maintenance and repair

    Why are fire dampers tested periodically?

    Show answer without guessing

    Answer: A. To confirm they close fully and are unobstructed

    Fire dampers can seize from dirt or corrosion, or be blocked by debris. Periodic inspection and drop testing at the frequency required by the fire code confirm they will close.

    Check it: RSOS task E-18 (scheduled maintenance)

  5. Question 5 · E – Performs maintenance and repair

    Which is a sign that a duct system needs inspection for cleaning?

    Show answer without guessing

    Answer: D. Visible dust or debris at outlets and in duct

    Dust discharging from outlets, debris in ducts or microbial growth indicate the need for inspection and possible cleaning to recognized industry standards.

    Check it: RSOS task E-18 (scheduled maintenance)

  6. Question 6 · E – Performs maintenance and repair

    A room is getting much less air than design. Which repair check comes first?

    Show answer without guessing

    Answer: D. Look for closed dampers, crushed flex or leaks

    Low airflow is usually caused by obstructions: closed or slipped dampers, kinked or crushed flex, disconnected duct or leaks. These are checked before any redesign.

    Check it: RSOS task E-19 (repairing faulty systems and components)

  7. Question 7 · E – Performs maintenance and repair

    A downspout has come loose from the wall. What is the correct repair?

    Show answer without guessing

    Answer: D. Refasten it with suitable straps and anchors

    Downspouts need straps fastened to the wall at intervals with anchors suited to the wall material, so wind, ice and water weight do not pull them off.

    Check it: RSOS task E-19 (repairing faulty systems and components)

  8. Question 8 · E – Performs maintenance and repair

    After a renovation, a branch duct was disconnected above the ceiling. How is this best found?

    Show answer without guessing

    Answer: D. Trace the branch and check flows at outlets

    Comparing measured outlet airflows to design and tracing the branch above the ceiling locates disconnections. Reconnecting and sealing restores airflow.

    Check it: RSOS task E-19 (repairing faulty systems and components)

These are VoltExam questions written for the Red Seal Sheet Metal Worker Interprovincial Exam, not official exam questions. Take the full free practice test or read the Red Seal Sheet Metal Worker (308A) guide.

Last checked against Red Seal Program (with provincial and territorial apprenticeship authorities) on .

Practise Red Seal Sheet Metal Worker (308A) by topic

Want every Red Seal Sheet Metal Worker (308A) topic and the timed mock exams?

  • ✓ 600 Red Seal Sheet Metal Worker practice questions, every answer explained and cited
  • ✓ Full-length timed mock exams: 120 questions, 4 hours, scored against 70%
  • ✓ Practise by topic and review every question you missed
  • ✓ Every other Canadian exam on VoltExam included

From

C$8.99/month

3-day free trial · or C$44.99 once for lifetime

Try all 600 free for 3 days

Free trial for new members on the Monthly plan, then C$8.99/month until you cancel. See all plans

Official sources

Sources checked November 14, 2026. VoltExam is independent and not affiliated with Red Seal Program (with provincial and territorial apprenticeship authorities). Rules change: confirm details with the official source before your exam.