Red Seal Electrician (309A): D – Motors and control systems practice questions
13 original questions on this part of the exam, each with an explanation and a reference you can check.
What this area covers (21 questions on the exam)
Motors, motor starters and protection, control circuits, drives and automated control systems.
Question 1 · D – Motors and control systems
What is the synchronous speed of a 4-pole, 60 Hz induction motor?
Show answer without guessing
Answer: C. 1800 r/min
Synchronous speed Ns = 120 × f ÷ P = 120 × 60 ÷ 4 = 1800 r/min. The rotor of an induction motor runs slightly slower than this because of slip.
Check it: RSOS MWA D – motors
Question 2 · D – Motors and control systems
A 6-pole, 60 Hz induction motor runs at 1140 r/min at full load. What is its slip?
Show answer without guessing
Answer: B. 5%
Ns = 120 × 60 ÷ 6 = 1200 r/min. Slip = (Ns − Nr) ÷ Ns = (1200 − 1140) ÷ 1200 = 60 ÷ 1200 = 0.05, or 5%.
Check it: RSOS MWA D – motors
Question 3 · D – Motors and control systems
A 600 V three-phase motor draws 20 A at a power factor of 0.85 and runs at 90% efficiency. What is its approximate mechanical output power?
Show answer without guessing
Answer: B. About 15.9 kW
Input power = √3 × 600 × 20 × 0.85 = 1039.2 × 20 × 0.85 ≈ 17 667 W. Output = input × efficiency = 17 667 × 0.90 ≈ 15 900 W ≈ 15.9 kW. 17.7 kW is the electrical input, and 20.8 kVA is the apparent power.
Check it: RSOS MWA D – motors
Question 4 · D – Motors and control systems
The conductors supplying a single continuous-duty motor must have an ampacity of at least what percentage of the motor's full-load current rating? For a 40 A motor, what does that give?
Show answer without guessing
Answer: C. 125%, giving 50 A
The CEC requires branch-circuit conductors for a single continuous-duty motor to be rated at no less than 125% of its full-load current: 40 A × 1.25 = 50 A. The extra margin allows for normal running above nameplate current without overheating the conductors.
Check it: CEC Rule 28-106 (conductors, single motor)
Question 5 · D – Motors and control systems
In a standard three-wire start/stop motor control circuit, how is the holding (seal-in) contact connected?
Show answer without guessing
Answer: B. As a normally open auxiliary contact of the starter wired in parallel with the start button
Pressing start energizes the coil, which closes the normally open auxiliary contact in parallel with the start button. That contact keeps the coil energized after the button is released. Pressing stop, an overload trip or a loss of voltage drops out the coil and opens the seal-in contact, so the motor will not restart on its own (low-voltage protection).
Check it: RSOS MWA D – motor control systems
Question 6 · D – Motors and control systems
What is the primary function of a motor overload relay?
Show answer without guessing
Answer: B. To protect the motor and its conductors from overheating caused by sustained running overcurrent
Overload relays respond to moderate overcurrent lasting long enough to overheat the motor, such as an overloaded or jammed drive or single-phasing. They use a time delay so normal starting current does not trip them. Short-circuit and ground-fault protection is provided separately by the branch-circuit fuses or breaker.
Check it: CEC Section 28 (motor overload protection)
Question 7 · D – Motors and control systems
A variable frequency drive feeds a 4-pole, 60 Hz motor. Approximately what output frequency gives a synchronous speed of 900 r/min?
Show answer without guessing
Answer: B. 30 Hz
Ns = 120 × f ÷ P, so f = Ns × P ÷ 120 = 900 × 4 ÷ 120 = 30 Hz. A VFD changes speed by changing frequency and normally reduces voltage in proportion (constant V/Hz) to keep magnetizing flux roughly constant.
Check it: RSOS MWA D – drives and control systems
Question 8 · D – Motors and control systems
How do you reverse the direction of rotation of a three-phase induction motor?
Show answer without guessing
Answer: D. Interchange any two of the three supply leads
Swapping any two line connections reverses the phase sequence, which reverses the direction of the rotating magnetic field and the motor. Rotating all three leads keeps the same sequence, and induction motors do not use a neutral.
Check it: RSOS MWA D – motors
Question 9 · D – Motors and control systems
Which control arrangement lets a motor restart automatically when power is restored after an outage?
Show answer without guessing
Answer: D. Two-wire control using a maintained-contact device such as a float or pressure switch
With two-wire control, the pilot device stays closed, so when voltage returns the coil re-energizes and the motor restarts (low-voltage release). Three-wire control drops out the seal-in contact on voltage loss and needs the start button pressed again (low-voltage protection).
Check it: RSOS MWA D – motor control systems
Question 10 · D – Motors and control systems
A motor fed by a VFD develops fluting damage on its bearings. What is the most likely cause?
Show answer without guessing
Answer: D. Shaft voltages induced by the drive's PWM output discharging through the bearings
PWM drives produce common-mode voltage that couples onto the motor shaft. When that voltage discharges through the bearing's lubricant film, it pits the races and creates a washboard (fluting) pattern. Shaft grounding rings, insulated bearings and proper bonding help prevent it.
Check it: RSOS MWA D – drives
Question 11 · D – Motors and control systems
A 37 kW, 600 V three-phase motor has 93% efficiency and 0.87 power factor at full load. What is its approximate full-load line current?
Show answer without guessing
Answer: A. About 44 A
Input power = 37 ÷ 0.93 = 39.8 kW. I = 39 800 ÷ (1.732 × 600 × 0.87) ≈ 44 A. Nameplate current should be used for protection when available.
Check it: RSOS task D-1 – motor calculations
Question 12 · D – Motors and control systems
A sequence control requires conveyor 2 to run before conveyor 1 can start. How is this commonly done in a hardwired circuit?
Show answer without guessing
Answer: C. Place a normally open auxiliary contact from conveyor 2's starter in series with conveyor 1's start circuit
Interlocking with an auxiliary contact ensures the downstream conveyor is running before material is fed to it. If conveyor 2 stops, the contact opens and conveyor 1 stops too.
Check it: RSOS task D-2 – sequence control
Question 13 · D – Motors and control systems
What is the difference between an absolute encoder and an incremental encoder after a power interruption?
Show answer without guessing
Answer: A. An absolute encoder reports the true position immediately; an incremental encoder must be homed again
Incremental encoders output pulses counted by the controller; the count is lost on power loss. Absolute encoders give a unique code for each position.
Check it: RSOS task D-5 – feedback devices
These are VoltExam questions written for the Red Seal Construction Electrician Interprovincial Exam, not official exam questions. Take the full free practice test or read the Red Seal Electrician (309A) guide.
Free calculators for this exam: Ohm's Law and Power Calculator, Metric Voltage Drop Calculator.
Last checked against Red Seal Program (with provincial and territorial apprenticeship authorities) on .
Practise Red Seal Electrician (309A) by topic
Want every Red Seal Electrician (309A) topic and the timed mock exams?
- ✓ 600 Red Seal Electrician practice questions, every answer explained and cited
- ✓ Full-length timed mock exams: 100 questions, 4 hours, scored against 70%
- ✓ Practise by topic and review every question you missed
- ✓ Every other Canadian exam on VoltExam included
From
C$8.99/month
3-day free trial · or C$44.99 once for lifetime
Try all 600 free for 3 daysFree trial for new members on the Monthly plan, then C$8.99/month until you cancel. See all plans
Official sources
- Red Seal – Construction Electrician trade page ↗
- Red Seal – Construction Electrician exam information (breakdown) ↗
- Red Seal – Exam Preparation Guide ↗
- Red Seal – Construction Electrician exam self-assessment guide (PDF) ↗
- CSA Group – CSA C22.1:24 Canadian Electrical Code, Part I (26th edition) ↗
- Skilled Trades Ontario – Electrician – Construction and Maintenance (309A) ↗
- Alberta Apprenticeship and Industry Training – Electrician trade profile ↗
- Saskatchewan Apprenticeship – Red Seal Written Examination Study Guide 2025 (PDF) ↗
Sources checked October 31, 2026. VoltExam is independent and not affiliated with Red Seal Program (with provincial and territorial apprenticeship authorities). Rules change: confirm details with the official source before your exam.