What this area covers (19 questions on the exam)
Work site preparation (5) and trade activities (14), which covers everyday skills such as trade calculations, piping and joining, and refrigerant handling.
Question 1 · B – Performs routine trade activities
The suction pressure at the evaporator outlet corresponds to a saturation temperature of 3°C. The suction line temperature at the same point is 9°C. What is the evaporator superheat?
Show answer without guessing
Answer: B. 6°C
Superheat is the actual vapour temperature minus the saturation temperature at the same pressure: 9°C − 3°C = 6°C. Adding the two (12°C) or using either reading alone does not describe how far the vapour is above its boiling point.
Check it: RSOS task B-6 (trade activities – calculations)
Question 2 · B – Performs routine trade activities
A condenser's saturated condensing temperature is 46°C (taken from the pressure-temperature chart at the measured head pressure). The liquid line temperature leaving the condenser is 39°C. What is the subcooling?
Show answer without guessing
Answer: A. 7°C
Subcooling is saturated condensing temperature minus actual liquid line temperature: 46°C − 39°C = 7°C. It shows how much the liquid has been cooled below its condensing point, which helps confirm a full column of liquid reaches the metering device.
Check it: RSOS task B-6 (trade activities – calculations)
Question 3 · B – Performs routine trade activities
A system shows a suction pressure of 350 kPa (gauge) and a discharge pressure of 1,480 kPa (gauge). Using 101 kPa for atmospheric pressure, what is the compression ratio?
Show answer without guessing
Answer: B. About 3.5:1
Compression ratio uses absolute pressures: (1,480 + 101) ÷ (350 + 101) = 1,581 ÷ 451 ≈ 3.5. Dividing gauge pressures (1,480 ÷ 350 ≈ 4.2) overstates the ratio, which is a common error.
Check it: RSOS task B-6 (trade activities – calculations)
Question 4 · B – Performs routine trade activities
Why is dry nitrogen flowed through copper refrigerant tubing while it is being brazed?
Show answer without guessing
Answer: B. To displace oxygen inside the tube so oxide scale does not form and later clog strainers and metering devices
Heating copper in the presence of air forms black oxide scale on the inside wall. Refrigerant and oil later loosen it, plugging filter driers, screens and expansion valves. A low nitrogen purge flow keeps oxygen out during brazing.
Check it: RSOS task B-6 (trade activities – brazing)
Question 5 · B – Performs routine trade activities
When filling a refillable refrigerant recovery cylinder, what is the generally accepted maximum fill level?
Show answer without guessing
Answer: D. 80% of liquid capacity, checked by scale or the cylinder's float or overfill sensor
Liquid refrigerant expands as it warms. Leaving at least 20% vapour space prevents a full liquid cylinder from building hydrostatic pressure that can rupture it. Weigh the cylinder against its marked tare and maximum fill or use an overfill shutoff.
Check it: RSOS task B-6 (refrigerant recovery)
Question 6 · B – Performs routine trade activities
At the outlet of a walk-in cooler evaporator, the suction pressure corresponds to a saturation temperature of 1°C on the pressure-temperature chart, and the suction line temperature measured at the same point is 7°C. What is the superheat?
Show answer without guessing
Answer: B. 6°C
Superheat = measured vapour temperature − saturation temperature at that pressure = 7 − (1) = 6°C. With below-zero temperatures, keep the signs: subtracting a negative saturation temperature adds its magnitude.
Check it: RSOS task B-6 (trade activities – calculations)
Question 7 · B – Performs routine trade activities
On a walk-in cooler condensing unit, the head pressure converts to a saturated condensing temperature of 46°C. The liquid line temperature measured at the condenser outlet is 36°C. What is the subcooling?
Show answer without guessing
Answer: B. 10°C
Subcooling = saturated condensing temperature − actual liquid temperature = 46 − 36 = 10°C. It tells you how far the liquid has been cooled below the temperature at which it condensed.
Check it: RSOS task B-6 (trade activities – calculations)
Question 8 · B – Performs routine trade activities
A compound gauge reads a vacuum of −60 kPa (gauge). Using 101 kPa for atmospheric pressure, what is the absolute pressure in the system?
Show answer without guessing
Answer: B. 41 kPa (absolute)
Absolute = gauge + atmospheric = −60 + 101 = 41 kPa. A vacuum is a negative gauge reading, so it is subtracted from atmospheric pressure; absolute pressure can never be negative.
Check it: RSOS task B-6 (trade activities – calculations)
Question 9 · B – Performs routine trade activities
Why are vibration isolators used under a compressor rack or condensing unit?
Show answer without guessing
Answer: C. To reduce transmission of vibration and noise to the building structure and piping
Rotating equipment transmits vibration that causes noise complaints, fatigue cracks in piping and loosened connections. Springs or pads matched to the load isolate it from the structure.
Check it: RSOS task B-5 (work site preparation)
Question 10 · B – Performs routine trade activities
When preparing a work site in a food store, what precaution protects product during service of a display case?
Show answer without guessing
Answer: D. Coordinate with the store to move or protect product and plan downtime to keep it at safe temperatures
Product spoilage is costly and a food safety issue. Planning with the customer to move product or schedule downtime prevents losses.
Check it: RSOS task B-5 (work site preparation)
Question 11 · B – Performs routine trade activities
Why must different refrigerants never be recovered into the same cylinder?
Show answer without guessing
Answer: C. Mixed refrigerants cannot easily be separated and may have to be destroyed rather than reclaimed
Reclaimers can process a single refrigerant to specification, but mixtures generally cannot be separated economically. Contaminated cylinders lead to high disposal costs.
Check it: RSOS task B-6 (refrigerant recovery and handling)
These are VoltExam questions written for the Red Seal Refrigeration and Air Conditioning Mechanic Interprovincial Exam, not official exam questions. Take the full free practice test or read the Red Seal Refrigeration Mechanic (313A) guide.
Last checked against Red Seal Program (with provincial and territorial apprenticeship authorities) on .
Practise Red Seal Refrigeration Mechanic (313A) by topic
Want every Red Seal Refrigeration Mechanic (313A) topic and the timed mock exams?
- ✓ 600 Red Seal Refrigeration Mechanic practice questions, every answer explained and cited
- ✓ Full-length timed mock exams: 125 questions, 4 hours, scored against 70%
- ✓ Practise by topic and review every question you missed
- ✓ Every other Canadian exam on VoltExam included
From
C$8.99/month
3-day free trial · or C$44.99 once for lifetime
Try all 600 free for 3 daysFree trial for new members on the Monthly plan, then C$8.99/month until you cancel. See all plans
Official sources
- Red Seal – Refrigeration and Air Conditioning Mechanic trade page ↗
- Red Seal – Refrigeration and Air Conditioning Mechanic exam information (breakdown) ↗
- Red Seal – Exam Preparation Guide ↗
- Skilled Trades Ontario – Refrigeration and Air Conditioning Systems Mechanic ↗
- Skilled Trades Ontario – Refrigeration and Air Conditioning Systems Mechanic (313A) 2025 trade report ↗
- Ontario – Certificate to handle refrigerants (ODP card) ↗
Sources checked November 14, 2026. VoltExam is independent and not affiliated with Red Seal Program (with provincial and territorial apprenticeship authorities). Rules change: confirm details with the official source before your exam.