Red Seal Refrigeration Mechanic (313A): F – Performs maintenance and service practice questions

13 original questions on this part of the exam, each with an explanation and a reference you can check.

What this area covers (28 questions on the exam)

Maintaining HVAC/R systems (8), servicing HVAC/R systems (11), and maintaining and servicing control systems (9): the largest area on the exam.

Answered 0 / 13Score 0
  1. Question 1 · F – Performs maintenance and service

    A system has high superheat, low suction pressure and low subcooling. The sight glass shows bubbles. What is the most likely cause?

    Show answer without guessing

    Answer: C. Low refrigerant charge, likely from a leak

    An undercharge starves the evaporator (high superheat, low suction pressure) and leaves too little liquid backed up in the condenser (low subcooling, bubbles in the glass). Find and repair the leak before weighing in the correct charge.

    Check it: RSOS task F-14 (services HVAC/R systems)

  2. Question 2 · F – Performs maintenance and service

    Head pressure is high, subcooling is high and the condenser fan and coil are clean and working. Superheat is normal to low. What is the most likely problem?

    Show answer without guessing

    Answer: D. The system is overcharged

    Excess refrigerant backs up as liquid in the condenser, reducing the surface left for condensing. That raises head pressure and subcooling. Recover refrigerant until superheat and subcooling match the manufacturer's charging data.

    Check it: RSOS task F-14 (services HVAC/R systems)

  3. Question 3 · F – Performs maintenance and service

    The temperature drop across a liquid line filter drier is 4°C. What does this indicate?

    Show answer without guessing

    Answer: A. The drier is partially restricted and should be replaced

    There should be little or no temperature drop across a liquid line drier. A noticeable drop means pressure is falling inside it, so some liquid flashes to vapour. Replace the drier after recovering or isolating the charge.

    Check it: RSOS task F-14 (services HVAC/R systems)

  4. Question 4 · F – Performs maintenance and service

    A residential condensing unit's run capacitor is rated 35 µF ± 6%. Which measured value shows the capacitor is still within tolerance?

    Show answer without guessing

    Answer: C. 34 µF

    6% of 35 µF is 2.1 µF, so the acceptable range is 32.9 to 37.1 µF. Only 34 µF falls within that range. Always discharge a capacitor safely before testing it.

    Check it: RSOS task F-15 (maintains and services control systems)

  5. Question 5 · F – Performs maintenance and service

    During routine maintenance on a refrigeration system, which task most directly helps prevent high head pressure?

    Show answer without guessing

    Answer: B. Cleaning the condenser coil and checking that the condenser fans run correctly

    A dirty condenser or a failed condenser fan reduces heat rejection, so condensing temperature and head pressure rise. That raises power draw and compressor discharge temperature. Coil cleaning and fan checks are core maintenance items.

    Check it: RSOS task F-13 (maintains HVAC/R systems)

  6. Question 6 · F – Performs maintenance and service

    A compressor contactor's coil is rated 24 V AC. With the thermostat calling for cooling, you measure 24 V across the coil but the contactor does not pull in. What is the most likely fault?

    Show answer without guessing

    Answer: C. The contactor coil is open or the contactor is mechanically stuck

    Correct voltage across the coil proves the control circuit has delivered power. If the contactor still does not close, the coil itself (check its resistance with power off) or the armature is at fault. A failed transformer or open safety switch would leave no voltage at the coil.

    Check it: RSOS task F-15 (maintains and services control systems)

  7. Question 7 · F – Performs maintenance and service

    Why should a compressor's windings be tested with a megohmmeter during service?

    Show answer without guessing

    Answer: D. To check the insulation resistance between the windings and ground for breakdown before it causes a short

    A megohmmeter applies a high DC test voltage and reads insulation resistance in megohms. Falling readings over time warn of moisture, acid or insulation damage. A standard ohmmeter uses too low a voltage to find weak insulation.

    Check it: RSOS task F-15 (motor diagnostics)

  8. Question 8 · F – Performs maintenance and service

    A crankcase heater measures 480 Ω (cold resistance taken as its operating resistance) and is supplied at 240 V. What power does it draw?

    Show answer without guessing

    Answer: C. 120 W

    P = V² ÷ R = 240² ÷ 480 = 57,600 ÷ 480 = 120 W. Current would be 240 ÷ 480 = 0.50 A, and P = V × I gives the same 120 W.

    Check it: RSOS task F-15 (electrical diagnostics)

  9. Question 9 · F – Performs maintenance and service

    A compressor nameplate lists an RLA of 18.5 A. You measure 24.0 A on the run lead at full load. What percentage of RLA is it drawing?

    Show answer without guessing

    Answer: D. About 130%

    24.0 ÷ 18.5 × 100 ≈ 130%. Sustained current well above RLA points to high head pressure, low voltage, mechanical wear or an overcharge and should be investigated.

    Check it: RSOS task F-14 (services HVAC/R systems)

  10. Question 10 · F – Performs maintenance and service

    During maintenance of a rooftop unit, why is the economizer damper and linkage checked?

    Show answer without guessing

    Answer: D. Seized or broken linkages can leave dampers stuck open or closed, wasting energy or reducing ventilation

    Economizers are a common failure point. A stuck-open damper brings in hot or cold air; a stuck-closed one loses free cooling and ventilation.

    Check it: RSOS task F-13 (maintains HVAC/R systems)

  11. Question 11 · F – Performs maintenance and service

    A system with a receiver and TXV has a clear sight glass, low suction pressure and high superheat. Head pressure is low in cold weather. What is the most likely cause?

    Show answer without guessing

    Answer: B. Head pressure too low to give the TXV enough pressure difference, so head pressure control should be checked

    In cold weather, without proper head pressure control, condensing pressure drops so far that the TXV cannot pass enough refrigerant. The evaporator starves even though liquid is available.

    Check it: RSOS task F-14 (services HVAC/R systems)

  12. Question 12 · F – Performs maintenance and service

    A thermistor reads 10 kΩ at 25°C. At a cold temperature it reads higher. What type of thermistor is it?

    Show answer without guessing

    Answer: A. Negative temperature coefficient (NTC)

    NTC thermistors' resistance falls as temperature rises and rises as it falls. Most HVAC sensors are NTC.

    Check it: RSOS task F-15 (maintains and services control systems)

  13. Question 13 · F – Performs maintenance and service

    When should you replace a compressor's start relay?

    Show answer without guessing

    Answer: D. When it fails to open or close at the right time, or shows burnt contacts

    Relays wear out. Faulty relays can leave the start capacitor in circuit or fail to start the motor.

    Check it: RSOS task F-15 (maintains and services control systems)

These are VoltExam questions written for the Red Seal Refrigeration and Air Conditioning Mechanic Interprovincial Exam, not official exam questions. Take the full free practice test or read the Red Seal Refrigeration Mechanic (313A) guide.

Last checked against Red Seal Program (with provincial and territorial apprenticeship authorities) on .

Practise Red Seal Refrigeration Mechanic (313A) by topic

Want every Red Seal Refrigeration Mechanic (313A) topic and the timed mock exams?

  • ✓ 600 Red Seal Refrigeration Mechanic practice questions, every answer explained and cited
  • ✓ Full-length timed mock exams: 125 questions, 4 hours, scored against 70%
  • ✓ Practise by topic and review every question you missed
  • ✓ Every other Canadian exam on VoltExam included

From

C$8.99/month

3-day free trial · or C$44.99 once for lifetime

Try all 600 free for 3 days

Free trial for new members on the Monthly plan, then C$8.99/month until you cancel. See all plans