Red Seal Refrigeration Mechanic (313A): D – Performs installation practice questions

12 original questions on this part of the exam, each with an explanation and a reference you can check.

What this area covers (26 questions on the exam)

Installing HVAC/R systems (16), such as compressors, condensers, evaporators, metering devices and piping, and installing control systems (10).

Answered 0 / 12Score 0
  1. Question 1 · D – Performs installation

    Which method is correct for adding a zeotropic blend such as R-407C to a system?

    Show answer without guessing

    Answer: A. Remove it from the cylinder as liquid and meter it into the system so it does not slug the compressor

    The components of a zeotropic blend boil at different temperatures, so drawing vapour off the top changes the mixture left in the cylinder and the composition charged. Taking liquid keeps the blend at its design ratio; meter it slowly into the suction side or charge into the liquid line with the system off.

    Check it: RSOS task D-9 (installs HVAC/R systems – charging)

  2. Question 2 · D – Performs installation

    When installing a thermostatic expansion valve, where is the sensing bulb normally attached?

    Show answer without guessing

    Answer: C. On the suction line near the evaporator outlet, in good contact and insulated from ambient air

    The TXV regulates refrigerant flow to hold a set superheat at the evaporator outlet, so its bulb must sense the suction line temperature there. It is clamped to a clean, straight, horizontal section and insulated so ambient air does not affect the reading.

    Check it: RSOS task D-9 (installs metering devices)

  3. Question 3 · D – Performs installation

    Why should a horizontal suction line be pitched slightly toward the compressor?

    Show answer without guessing

    Answer: A. So oil carried by the refrigerant drains toward the compressor instead of pooling in the line

    Oil leaves the compressor with the discharge gas and must return through the suction line. A slight pitch in the direction of flow helps gravity move oil to the compressor, especially at low loads when vapour velocity drops.

    Check it: RSOS task D-9 (installs piping)

  4. Question 4 · D – Performs installation

    After brazing is complete on a new installation, which gas should be used to pressure-test the system for leaks?

    Show answer without guessing

    Answer: B. Dry nitrogen, regulated to a pressure no higher than the system's rated test pressure

    Oxygen can react violently with compressor oil and cause an explosion, and compressed air adds moisture. Dry nitrogen is inert and dry. Always use a regulator and relief device and do not exceed the test pressure on the equipment nameplate.

    Check it: RSOS task D-9 (installs HVAC/R systems – pressure testing)

  5. Question 5 · D – Performs installation

    You are wiring a single-phase compressor and measure these resistances: C to R = 2 Ω, C to S = 5 Ω, R to S = 7 Ω. Which terminal is S (start)?

    Show answer without guessing

    Answer: D. The terminal that reads 5 Ω to common and is part of the highest (7 Ω) reading

    The highest reading (7 Ω) is across both windings, R to S, so the third terminal is common. From common, the lower resistance (2 Ω) is the run winding and the higher (5 Ω) is the start winding. Note 2 + 5 = 7, which confirms the windings are intact.

    Check it: RSOS task D-10 (installs control systems – motors)

  6. Question 6 · D – Performs installation

    When installing a split air-conditioning system, why is a trap commonly installed in the evaporator condensate drain line on a draw-through coil?

    Show answer without guessing

    Answer: B. The cabinet is under negative pressure, so the trap seals the drain, stopping air being drawn in and holding water in the pan

    With the fan pulling air through the coil, the drain pan sits under suction. Without a water seal, air rushes up the drain and condensate cannot leave, which can overflow the pan or blow water into the duct. A properly sized trap and slope prevent this.

    Check it: RSOS task D-9 (installs HVAC/R systems – condensate)

  7. Question 7 · D – Performs installation

    A 40 VA, 24 V control transformer will supply relay and contactor coils that draw a total of 1.3 A. What is the transformer's rated secondary current, and is it adequate?

    Show answer without guessing

    Answer: B. About 1.7 A; adequate

    Rated secondary current = VA ÷ volts = 40 ÷ 24 ≈ 1.7 A. The connected load of 1.3 A is within this rating. Coil inrush is several times the holding current, so leave margin.

    Check it: RSOS task D-10 (installs control systems)

  8. Question 8 · D – Performs installation

    Which direction should the arrow on a liquid line solenoid valve point?

    Show answer without guessing

    Answer: D. In the direction of refrigerant flow

    Solenoid valves rely on pressure difference to seat properly. Installed backwards, they may leak through or fail to close.

    Check it: RSOS task D-9 (installs HVAC/R systems)

  9. Question 9 · D – Performs installation

    When installing a ductless multi-zone system, why must each line set be connected to the correctly labelled outdoor ports and matching wiring?

    Show answer without guessing

    Answer: D. Mismatched piping and wiring send refrigerant to one zone while controls serve another, causing faults

    Each zone's piping and communication wiring must match. Cross-connection leads to one indoor unit icing while another gets no cooling. Many units have a wiring check function, but the installer must verify it.

    Check it: RSOS task D-9 (installs HVAC/R systems)

  10. Question 10 · D – Performs installation

    When installing a potential relay for a single-phase compressor with a start capacitor, how is the relay coil connected?

    Show answer without guessing

    Answer: D. Between the start terminal and common, sensing the voltage generated across the start winding

    As the motor reaches speed, back EMF across the start winding rises and pulls in the potential relay coil, opening its normally closed contacts and removing the start capacitor.

    Check it: RSOS task D-10 (installs control systems)

  11. Question 11 · D – Performs installation

    When installing a crankcase heater on a compressor, how is it usually wired?

    Show answer without guessing

    Answer: A. Energized during the compressor's off cycle, often through a normally closed contact or as specified

    Crankcase heaters keep oil warmer than the rest of the system so refrigerant does not migrate into it. They are typically energized when the compressor is off.

    Check it: RSOS task D-10 (installs control systems)

  12. Question 12 · D – Performs installation

    What is the main purpose of a service valve on a condensing unit?

    Show answer without guessing

    Answer: A. To isolate the unit and provide gauge access for service

    Service valves let technicians isolate parts of a system to hold the charge during repairs and attach gauges for readings and charging.

    Check it: RSOS task D-9 (installs HVAC/R systems)

These are VoltExam questions written for the Red Seal Refrigeration and Air Conditioning Mechanic Interprovincial Exam, not official exam questions. Take the full free practice test or read the Red Seal Refrigeration Mechanic (313A) guide.

Last checked against Red Seal Program (with provincial and territorial apprenticeship authorities) on .

Practise Red Seal Refrigeration Mechanic (313A) by topic

Want every Red Seal Refrigeration Mechanic (313A) topic and the timed mock exams?

  • ✓ 600 Red Seal Refrigeration Mechanic practice questions, every answer explained and cited
  • ✓ Full-length timed mock exams: 125 questions, 4 hours, scored against 70%
  • ✓ Practise by topic and review every question you missed
  • ✓ Every other Canadian exam on VoltExam included

From

C$8.99/month

3-day free trial · or C$44.99 once for lifetime

Try all 600 free for 3 days

Free trial for new members on the Monthly plan, then C$8.99/month until you cancel. See all plans